600/1000V XLPE绝缘,PVC护套,双钢带铠装电力缆 (3芯)

应用600/1000V XLPE绝缘,PVC护套,双钢带铠装电力缆主要应用于发电站、公共交通客运系统、机场、石化工厂、酒店、医院、高层建筑等的配线电缆。标准标准适应 IEC 60502-1防火性能阻
  • 电 话:0550-7773008
  • 邮件:ahhyjt@yeah.net
Description

应用

600/1000V XLPE绝缘,PVC护套,双钢带铠装电力缆主要应用于发电站、公共交通客运系统、机场、石化工厂、酒店、医院、高层建筑等的配线电缆。

标准

标准适应 IEC 60502-1

防火性能

阻燃性(单根垂直线缆测试)EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
降低火蔓延(垂直安装的成束电缆测试)EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24;VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22I3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
无卤IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI 20-37/2-1; BS 6425-1*
无腐蚀性气体排放IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI 20-37/2-2; BS 6425-2*
***小烟雾释放IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
无有毒气体NES 02-713; NF C 20-454

注:*表示该标准已经被取代

额定电压

600/1000V

线缆结构

导体平纹退火铜,多股绞合符合IEC(EN) 60228 class 2
绝缘交联聚乙烯复合物
填料,粘合剂(其他)PP,PET, PVC
铠装双钢带
外护套热塑性PVC复合物,抵抗紫外线, 耐碳氢化合物、耐油、反啮齿动物和抗白蚁属性可以被作为选项。符合防火性能标准(IEC 60332 - 1,IEC 60332 - 3,UL 1581,UL 1666等)取决于氧指数的PVC复合物的全方位电缆设计。LSPVC也可以根据要求提供。

色谱

绝缘颜色遵循标准 BS7671

 带接地导体不带接地导体
2芯-棕色, 蓝色
3芯黄绿线, 棕色,蓝色棕色, 灰色, 黑色
4芯黄绿线,棕色,灰色,黑色棕色, 灰色, 黑色, 蓝色
5芯黄绿线,棕色,灰色,黑色, 蓝色棕色, 灰色, 黑色, 蓝色, 黑色
5芯以上黄绿线, 黑色数根黑色数根

护套颜色:黑色或根据客户要求

物理性能和热性能

工作温度范围***大90°C对于XLPE
 短路过载温度可达250°C(5s)
***小弯曲半径10 x 总外径

结构参数

导体FGD400 1RVMV-R
芯数I截面积相线中线标称导体外径标称绝缘厚度标称钢带厚度标称护套厚度标称总外径大约重量
股数/单丝直径股数/单丝直径PHA.NEU.PHA.NEU.
MM²NO/MMNO/MMMMMMMMMMMMMMMMKGIKM
3×10+1×67/1.357/1.043.752.900.70.70.21.820.1740
3×16+1×107/1.707/1.354.753.750.70.70.21.822.51,004
3×25+2×167/2.147/1.705.854.750.90.70.21.825.81,421
3×35+1×167/2.527/1.706.904.750.90.70.21.827.71,745
3×35+1×257/2.527/2.146.905.850.90.90.21.828.61,864
3×50+1×2519/1.787/2.148.155.851.00.90.21.831.32,358
3×50+1×3519/1.787/2.528.156.901.00.90.21.932.02.72
3×70+1×3519/2.147/2.529.756.901.10.90.22.035.93166
3×70+1×5019/2.1419/1.789.758.151.11.00.22.036.83.341
3×95+1×5019/2.5219/1.7811.48.151.11.00.52.141.44,611
3×120+1×7037/2.0319/2.1412.89.751.21.10.52.345.65682
3×150+1×9537/2.2519/2.5214.311.41.41.10.52.450.87,072
3×150+1×12037/2.2537/2.0314.312.81.41.20.52.551.87,357
3×185+1×9537/2.5219/2.5215.911.41.61.10.52.654.78,348
3×185+1×12037/2.5237/2.0315.912.81.61.20.52.655.88638
3×240+1×12061I2.2537/2.0318.212.81.71.20.52.761.010,660
3×240+1×15061I2.2537/2.2518.214.31.71.40.52.862.211024
3×300+1×15061I2.5237/2.2520.414.31.81.40.52.966.812,809
3×300+1×18561I2.5237/2.5220.415.91.81.60.53.068.113,256

电气性能

芯数I截面积导体***大导体直流阻抗 @20°C
相线中线总外径
股数/单丝直径股数/单丝直径PHA.NEU.PHA.NEU.
MM²NOIMMNOIMMMMMMΩIKMΩIKM
3×10+1×67/1.357/1.043.752.901.833.08
3×16+1×107/1.707/1.354.753.751.151.83
3×25+2×167/2.147/1.705.854.750.7271.15
3×35+1×167/2.527/1.706.904.750.5241.15
3×35+1×257/2.527/2.146.905.850.5240.727
3×50+1×2519/1.787/2.148.155.850.3870.727
3×50+1×3519/1.787/2.528.156.900.3870.524
3×70+1×3519/2.147/2.529.756.9002680.524
3×70+1×5019/2.1419/1.789.758.1502680.387
3×95+1×5019/2.5219/1.7811.48.150.1930.387
3×120+1×7037/2.0319/2.1412.89.750.1530.268
3×150+1×9537/2.2519/2.5214.311.40.1240.193
3×150+1×12037/2.2537/2.0314.312.80.1240.153
3×185+1×9537/2.5219/2.5215.911.40.09910.193
3×185+1×12037/2.5237/2.0315.912.80.09910.153
3×240+1×12061/2.2537/2.0318.212.80.07540.153
3×240+1×15061/2.2537/2.2518.214.30.07540.124
3×300+1×15061/2.5237/2.2520.414.30.06010.124
3×300+1×18561/2.5237/2.5220.415.90.06010.0991

电气性能

导体操作温度90°C
周围环境30°C

载流容量 (Amp)

导体参考方法1(直接用夹子夹住)参考方法11(在一个有孔径的电缆匣中,垂直或者水平)装于单层管道处直接敷设于地下
2根电缆单相交流或者直流电3根或者4根电缆三相交流电2根电缆单相交流或者直流电3根或者4根电缆三相交流电2根电缆单相交流或者直流电3根或者4根电缆三相交流电2根电缆单相交流或者直流电3根或者4根电缆三相交流电
截面积
123456789
MM²AAAAAAAA
1085739078-65-80
16110941159911594140115
25146124152131145125180150
35180154188162175150215180
50219187228197210175255215
70279238291251260215315265
95338289354304310260380315
120392335410353355300430360
150451386472406400335480405
185515441539463455380540460
240607520636546520440630530
300698599732628590495700590

电压降(AIM)

导体截面积2根电缆直流电2根电缆单相交流电3或4根电缆3相交流电2根电缆单相交流电3或4根电缆3相交流电
管道或地下管道或地下
123456
MM²MV/A/MMV/A/MMV/A/MMV/A/MMV/A/M
67.97.96.87.96.5
104.74.74.04.73.9
162.92.92.52.92.6


rxzrxz

251.8501.3500.1601.9001.6000.1401.6501.9001.600
351.3501.3500.1551.3501.1500.1351.1501.3501.200
500.9800.9900.1551.0000.8600.1350.8701.0000.870
700.6700.6700.1500.6900.5900.1300.6000.6900.610
950.4900.5000.1500.5200.4300.1300.4500.5200.450
1200.3900.4000.1450.4200.3400.1300.3700.4200.360
1500.3100.3200.1450.3500.2800.1250.3000.3500.300
1850.2500.2600.1450.2900.2200.1250.2600.2900.250
2400.1950.2000.1400.2400.1750.1250.2100.2400.210
3000.1550.1600.1400.2100.1400.1200.1850.2100.190
4000.1200.1300.1400.1900.1150.1200.1650.1900.180

注: